T.3.4 Screen is black/initial screen is not displayed

Is the status LED green? Is it showing the breathing LED status?

Cause

For cases in which the standby mode settings are performed, there is a possibility that it is set in the standby mode (screen OFF).

Solution

Please touch the screen only once. For cases in which the screen is not displayed even when touched, verify the following system data area.

Is "FFFFh" written in the system data area [Screen Display ON/OFF] address?

Cause

When "FFFFh" is stored in the [Screen Display ON/OFF] address, the screen display is turned OFF.

Solution

Store "Oh" in the [Screen Display ON/OFF] address. For more information regarding the System Data Area settings, refer to the following.
5.4.6 System Settings [Display Unit] - [System Area] Settings Guide

When the system data area [Control] address bit 0 is turned ON.

Cause

When bit 0 of the [Control] address is turned O, the backlight is turned off.

Solution

Turn OFF the [Control] address bit 0. For more information regarding the System Data Area settings, refer to the following.
5.4.6 System Settings [Display Unit] - [System Area] Settings Guide

Is the status LED light flashing orange?

Cause

For models that support a backlight burnout detection function, backlight burnout is detected.

For models that support backlight burnout detection, please refer to the following.
1.5 Supported Features

Solution

Replace the backlight. If there is no improvement, please contact the Pro-face customer care center.

Moreover, when the status LED is turned on in orange soon after purchase, there is a possibility that the display unit is out of order. Please contact the Pro-face customer care center.


T.11.2 Telephone Contact

Is the status LED showing something other than the breathing LED status? (For GP4000 series)

Cause

For the GP4000 series (excluding the GP-4100 series, GP-4201TM series, GP-4301 series), when the screen is dark and the status LED is either off or in a state other than the breathing LED status, the backlight may be burned out.

Solution

Please contact the Pro-face customer care center.

Is the status LED turned OFF?

Cause

The power supply voltage to the display unit is low.

Solution

Measure the power voltage of each display unit and set it according to the "Rated Voltage Range" specified in the manual or the hardware manual. If it does not improve even if it is set within the range, there is a possibility that it is out of order. Please contact the Pro-face customer care center.


T.11.2 Telephone Contact

Are errors displayed?

Cause

When the error message "RAAA005 The specified initial screen number does not exist" is displayed, the initial screen number (initial screen) displayed when turning on the power may be incorrect.

Solution

Confirm the setting of the initial screen number. Refer to the following for the setting change method.

M.2.6 Setting the number of the screen that is initially displayed after the power is turned ON