T.9.1 Errors displayed when Web Server is accessed

Error Code

Error Message

Cause and Troubleshooting

Browse

RFAF005

Select device name

The monitor was started without [Connection Device Name] selected in [Device View]. Select a connection device name in [Device View].

37.20.1.7 Standard Template HTML - Main Frame / [Device View] Page

RFAF006

Enter device address

The monitor was started without [Device Address] selected in [Device View].
Select [Device Address] in [Device View].

37.20.1.7 Standard Template HTML - Main Frame / [Device View] Page

RFAF007

Select access points

The monitor was started without [Access Points] selected in [Device View]. Select [Access Points] in [Device View].

37.20.1.7 Standard Template HTML - Main Frame / [Device View] Page

RFAF008

Select data type

The monitor was started without [Data Type] selected in [Device View]. Select [Data Type] in [Device View].

37.20.1.7 Standard Template HTML - Main Frame / [Device View] Page

RFAF009

Select update cycle

The monitor was started without [Update Cycle] selected in [Device View]. Select [Update Cycle] in [Device View].

37.20.1.7 Standard Template HTML - Main Frame / [Device View] Page

RFAF010

Insufficient memory

No Memory is set. Forcibly transfer the system using GP-Pro EX. If this error still occurs despite forcibly transferring the system, reduce the screen data capacity.*1

34.12.1 Transfer Settings Guide

RFAF011

Invalid request

The cause of this error may be that the URL was edited and an invalid request was sent. Transfer the standard HTML template again using [Site Transmission] in [Transfer Tool]. Alternatively, you can run forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF024

Invalid URL

The cause of this error may be that the URL was edited and an invalid request was sent. Make sure that the folder specified in the Web folder of [Remote Monitoring Settings] in the System Settings exists in external storage. Alternatively, transfer again the standard HTML template using [Site Transmission] in [Transfer Tool], or run a forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF026

Cannot open URL

The cause of this error may be that the URL was edited and an invalid request was sent. Make sure the Web folder you specified from the [System Settings] node's [Remote Monitoring Settings] exists on external storage. Alternatively, transfer the standard HTML template again using the [Transfer Tool]'s [Site Transmission] setting, or run a forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF028

Cannot stat page for URL

The cause of this error may be that the URL was edited and an invalid request was sent. Make sure the Web folder you specified from the [System Settings] node's [Remote Monitoring Settings] exists on external storage. Alternatively, transfer the standard HTML template again using the [Transfer Tool]'s [Site Transmission] setting, or run a forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF030

Missing form name

The cause of this error may be that the path after /goform/ was specified incorrectly and accessed. Transfer the standard HTML template again using [Site Transmission] in [Transfer Tool] or run a forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF031

Form (*****) is not defined. Form Name: *****

The cause of this error may be that the path after /goform/ was specified incorrectly and accessed. Transfer the standard HTML template again using the [Transfer Tool]'s [Site Transmission] setting or run a forced transfer of the system from GP-Pro EX.*2

34.12.1 Transfer Settings Guide

RFAF040

Access Denied. Wrong Password

The password may be incorrect. Enter the correct user ID and password. Also check if settings such as whether only the password is used or whether both the user ID and password are used is correct.*2

-

RFAF041

Access to this document requires a password

The cause of this error may be that the document was accessed via a new window and the password is incorrect. Enter the correct user ID and password. Also check if settings such as whether only the password is used or whether both the user ID and password are used are correct.*2

-

RFAF042

Access to this document requires a User ID

The cause of this error may be that the document was accessed via a new window and the user ID is incorrect. Enter the correct user ID and password. Also check if settings such as whether only the password is used or whether both the user ID and password are used are correct.*2

-

RFAF049

Cannot open template file

The standard HTML template is deleted. Make sure that the folder specified in the Web folder of [Remote Monitoring Settings] in the System Settings exists in external storage. Alternatively, transfer again the standard HTML template using [Site Transmission] in [Transfer Tool], or run a forced transfer of the system from GP-Pro EX.*1

37.20.2 System Settings - Display Unit - Remote Viewer Settings Guide

RFAF051

Failed to get device address

An incorrect [Device] is set. Set the correct [Device].

-

RFAF052

Failed to read device

An attempt was made to read the device that is not communicating with the connection device. Set the correct [Device]. Alternately, make sure that the Display and connection device are correctly connected.

-

RFAF053

Failed to write device

An attempt was made to write the device that is not communicating with the connection device. Set the correct [Device]. Alternately, make sure the Display and equipment are connected correctly.

-

RFAF054

Entered data is not consistent with Data Type.

Data was written that differs from the data type set in [Data Type]. Enter the correct data.

-

RFAF055

Entered data is too much.

Data beyond the limit was written to the set [Data Type]. Enter the correct amount of data.

37.10.3 Operation - Displaying and Editing Addresses Via Web Server

RFAF056

Enter data.

Blank data was entered. Enter the correct amount of data.

-

RFAF057

In the server settings [Write Web Server Data] is disabled. This operation will not run.

To enable writing, from the [Common Settings] select [Security], [Passwords], and [Set Security Level For Each Feature], then in the [Write Web Server Data] area clear the [Disable] check box.

23.10.1.1 Password Settings

RFAF064

Failed to read alarm information

The cause of this error may be that alarm information is not set and the alarm list is collected. Check alarm settings using GP-Pro EX.*1

20. Alarms

RFAF065

Executing other request

SRAM is being accessed by the display unit. Wait for several minutes and try updating again.*1

-

*1 After restoring the error, do not use the browser's [Return] button. Instead, access from the Web Server's [Welcome] screen.

*2 After restoring the error, do not use the browser's [Return] button. Instead, type the URL for the Web Server.