T.3.7 The status LED is flashing in green

Is the logic program running?

Cause

If the status LED is flashing in green in logic execution mode, the logic program may have stopped.

Solution

Disable the logic program according to the following procedure.

  1. When performing with GP-Pro EX
    , select [Logic Programs] from [System Settings] and select [Disable]. When using LT Enter offline mode.

  2. Display Unit
    Select [Off] in [Logic Program] from [Logic]. Save the setting and then exit offline mode.
    M.24.2.1 Main Unit - Logic Settings

Run the logic program according to the following procedure.

  1. When performing with GP-Pro EX
    , select [Display Unit] from [System Settings]. In the [Logic] tab, set [Logic Program Operation] to [RUN]. Transfer the project file to the Display. When using LT Enter offline mode.

  2. Display Unit
    In offline mode, select [Main Unit], [Logic]. Set [Logic Program] to [RUN]. Save the setting and then exit offline mode.
    M.24.2.1 Main Unit - Logic Settings