For pulse outputs, when combining the number of CH and high-speed counters used, there is a limit to the maximum output frequency in the LT3000 Series.
While the pulse output maximum frequency is 65000 Hz, when combined with how many CH and high-speed counters are used as illustrated in the following table, there is a limit to the output frequency setting.
For example, when using 3 pulse output CH and 1 high-speed counter CH, the maximum output frequency per CH is 27027 Hz.
Pulse Output 1CH Maximum Frequency
| 
 | Pulse output | ||||
|---|---|---|---|---|---|
| 1 CH | 2 CH | 3 CH | 4 CH | ||
| High Speed Counter | Do Not Use | 65000 Hz | 45454 Hz | 30303 Hz | 22727 Hz | 
| 1 CH | 65000 Hz | 38461 Hz | 27027(Hz) | — | |
| 2 CH | 52631(Hz) | 33333(Hz) | — | — | |
| 3 CH | 43478(Hz) | — | — | — | |
| 4 CH | — | — | — | — | |
* "-" indicates cannot use.
* 2-phase counter has a maximum 2CH. In the table, 3 CH is for single phase counters.
Verification of these limits occur when the LT starts up and when parameters change.
When an error arises, error information is stored in the system variable (#L_ExIOSpParmErr). For details, see 31.5.9.4 Abnormal Status of Normal Pulse Output - Normal Pulse Output (LT Series)