The analog output module defines output range, customizable value, and fallback value using configuration object.
Channel |
Object (Hex) |
Sub index |
Description |
Parameter |
CH1 |
2200 |
n |
Data Format |
0: Disable 4: Voltage (-10 to 10V) |
2201 |
n |
Data range |
0: Fixed 1: User setting |
|
2202 |
n |
Lower limit |
Lowest value |
|
2203 |
n |
Upper limit |
Highest value |
|
6411 |
n |
Written value |
Output |
|
6443 |
n |
Fallback mode |
0: Retentive State 1: Fallback |
|
6444 |
n |
Fallback Value (when 6443h = 1) |
Fallback Value |
|
CH2 |
Same as CH1. Sub index is n+1. |