The analog I/O module defines the I/O range, customizable values, fallback mode, and fallback value.
Analog channels can be mixed.
Channel |
Object (Hex) |
Sub index |
Description |
Parameter |
CH1 (Input) |
2100 |
n |
Data Format |
0: Disable 2: Current (4 to 20mA) 3: Voltage (0 to 10V) |
2101 |
n |
Data range |
0: Fixed 1: User setting |
|
2102 |
n |
Lower limit |
Lowest value |
|
2103 |
n |
Upper limit |
Highest value |
|
6401 |
n |
Read value |
Input |
|
6422 |
1 |
PDO transmission channel number |
|
|
6423 |
0 |
PDO transmission enabled/disabled |
0: Disable PDO transmission 1: Enable PDO transmission |
|
CH2 (Input) |
Same as CH1 (Input). Sub index is n+1. |
|||
CH1 (Output) |
2200 |
n |
Data Format |
0: Disable 2: Current (4 to 20mA) 3: Voltage (0 to 10V) |
2201 |
n |
Data range |
0: Fixed 1: User setting |
|
2202 |
n |
Lower limit |
Lowest value |
|
2203 |
n |
Upper limit |
Highest value |
|
6411 |
n |
Written value |
Output |
|
6443 |
n |
Fallback mode |
0: Retentive State 1: Fallback |
|
6444 |
n |
Fallback Value (when 6443h = 1) |
Fallback Value |