Specify the output frequency. You can use 10Hz to 65kHz for setting the output frequency.
When using normal pulse, set [Acceleration/Deceleration Time] to 0 in the LT3000 Series. In the LT4000 Series, set [Acceleration time] and [Deceleration time] to 0.
Set Up Process in GP-Pro EX
LT3000 Series
From the [Project] menu, point to [System Settings] and click [I/O Driver]. On the [Int.Driver 1] tab, click [Pulse Settings].
Specify the [Output Frequency] in the [Pulse Settings] dialog box.
LT4000 Series
From the [Project] menu, point to [System Settings] and click [I/O Driver]. Select [PLS] in [Function].
Set the output frequency in the [Output Frequency].
Set Up Process with System Variables
Define the output frequency in the system variable (#L_PLS*_LHZ). The system variable name adjusts to match the CH pulse output to which it's mapped.