Project data error
Error Code |
Error Message |
Description |
Solution |
001 |
Module type error |
Logic stop error The module setting type is not supported |
The project file might not have been sent properly. Transfer the project file again. |
002 |
Setting value error |
Logic stop error The variable mapped to the terminal is incorrect. Invalid terminal settings |
|
003 |
Device out-of-range error |
Logic stop error The variable address allocated to the terminal is not correct. |
|
004 |
Excess terminal settings |
Logic stop error The number of terminals is not correct. (Too many terminals) |
|
005 |
Terminal setting order error |
Logic stop error The terminal no. is not in ascending order. |
|
006 |
Terminal registry short |
Logic stop error The number of terminals is not correct. (Too few terminals) |
|
007 |
Module settings duplicated |
Logic stop error The module is registered twice. |
|
008 |
Excess module settings |
Logic stop error The number of modules is not correct. (Too many modules) |
|
009 |
Driver settings duplicated |
Logic stop error The driver is registered twice. |
|
010 |
I/O settings inconsistent |
Logic stop error The terminal settings are not correct (Module I/O settings are not consistent). |
|
011 |
Bit/Integer type inconsistent |
Logic stop error The terminal settings are not correct (Module variable type settings are not consistent). |
|
012 |
Setting level value error |
Logic stop error The driver is not correct. |
|
013 |
Data obtaining address error |
Logic stop error The driver information is in correct. The controller information is not correct. |
|
014 |
Driver ID error |
Logic stop error The driver/Module registry results in an error and have not been registered. |
|
015 |
Module setting order error |
Logic stop error The module number is not in ascending order. |
|
016 |
File Version Error |
Logic stop error Not compatible with the driver's file version |
H/W related error
Error Code |
Error Message |
Description |
Solution |
050 |
I/O board ID different |
Logic stop error The connected I/O board is not correct. |
The display type might not be correct. Check the display type and transfer the project file again. |
051 |
Unsupported model error |
Logic stop error The driver does not support the model. |
|
052 |
IO initial error |
Logic stop error The I/O board initialization fails. |
The project file may not have been sent correctly. Transfer the project file again. If the problem is still not solved, there may be a problem with the hardware. If the problem continues, please contact our customer care center. |
053 |
IO ROM error |
Logic stop error There is a problem with the system ROM on the I/O board. |
|
054 |
IO RAM error |
Logic stop error There is a problem with the system RAM on the I/O board. |
|
055 |
IO microcomputer error |
Logic stop error There is a problem with the microcomputer on the I/O board. |
|
056 |
IO IF RAM error |
Logic stop error There is a problem with the system I/F RAM on the I/O board. |
|
057 |
IO E2PROM error |
Logic stop error There is a problem with the system E2PROM on the I/O board. |
Application error
Error Code |
Error Message |
Description |
Solution |
100 |
I/O board error |
Logic stop error The I/O board does not respond. |
The project file may not have been sent correctly. Transfer the project file again. If this does not resolve the problem, the module itself may be broken. If the problem continues, please contact our customer care center. |
101 |
Special IO parameter error |
I/O update continuing error There is a problem with the special I/O parameter you set. |
The parameter is not correct. Reset the parameter and request the parameter change. |
102 |
Acceleration/Deceleration table creation error |
I/O update continuing error There is a problem with the special I/O parameter you set. |
The parameter is not correct. Reset the parameter and request the acceleration/deceleration table creation. |
103 |
Initial parameter error |
I/O update continuing error There is a problem with the special I/O parameter during initial processing. |
The parameter is not correct. It will be returned to the initial value set with the editor. Reset the parameter and request the parameter change. |
Internal error
Error Code |
Error Message |
Description |
Solution |
200 |
Integer type data read error. |
I/O update continuing error Reading the integer type terminal data value failed. |
The project file may not have been sent correctly. Transfer the project file again. |
201 |
Bit type data read error |
I/O update continuing error Reading the bit type terminal data value failed. |
|
202 |
Integer type data write error |
I/O update continuing error Writing the integer type terminal data value failed. |
|
203 |
Bit type data write error |
I/O update continuing error Writing the bit type terminal data value failed. |