31.5.13.1 Error Code (LT Series)

Project data error

Error Code

Error Message

Description

Solution

001

Module type error

Logic stop error

The module setting type is not supported

The project file might not have been sent properly.

Transfer the project file again.

002

Setting value error

Logic stop error

The variable mapped to the terminal is incorrect.

Invalid terminal settings

003

Device out-of-range error

Logic stop error

The variable address allocated to the terminal is not correct.

004

Excess terminal settings

Logic stop error

The number of terminals is not correct. (Too many terminals)

005

Terminal setting order error

Logic stop error

The terminal no. is not in ascending order.

006

Terminal registry short

Logic stop error

The number of terminals is not correct. (Too few terminals)

007

Module settings duplicated

Logic stop error

The module is registered twice.

008

Excess module settings

Logic stop error

The number of modules is not correct. (Too many modules)

009

Driver settings duplicated

Logic stop error

The driver is registered twice.

010

I/O settings inconsistent

Logic stop error

The terminal settings are not correct (Module I/O settings are not consistent).

011

Bit/Integer type inconsistent

Logic stop error

The terminal settings are not correct (Module variable type settings are not consistent).

012

Setting level value error

Logic stop error

The driver is not correct.

013

Data obtaining address error

Logic stop error

The driver information is in correct.

The controller information is not correct.

014

Driver ID error

Logic stop error

The driver/Module registry results in an error and have not been registered.

015

Module setting order error

Logic stop error

The module number is not in ascending order.

016

File Version Error

Logic stop error

Not compatible with the driver's file version

 

H/W related error

Error Code

Error Message

Description

Solution

050

I/O board ID different

Logic stop error

The connected I/O board is not correct.

The display type might not be correct.

Check the display type and transfer the project file again.

051

Unsupported model error

Logic stop error

The driver does not support the model.

052

IO initial error

Logic stop error

The I/O board initialization fails.

The project file may not have been sent correctly.

Transfer the project file again.

If the problem is still not solved, there may be a problem with the hardware. If the problem continues, please contact our customer care center.

053

IO ROM error

Logic stop error

There is a problem with the system ROM on the I/O board.

054

IO RAM error

Logic stop error

There is a problem with the system RAM on the I/O board.

055

IO microcomputer error

Logic stop error

There is a problem with the microcomputer on the I/O board.

056

IO IF RAM error

Logic stop error

There is a problem with the system I/F RAM on the I/O board.

057

IO E2PROM error

Logic stop error

There is a problem with the system E2PROM on the I/O board.

 

Application error

Error Code

Error Message

Description

Solution

100

I/O board error

Logic stop error

The I/O board does not respond.

The project file may not have been sent correctly.

Transfer the project file again.

If this does not resolve the problem, the module itself may be broken. If the problem continues, please contact our customer care center.

101

Special IO parameter error

I/O update continuing error

There is a problem with the special I/O parameter you set.

The parameter is not correct. Reset the parameter and request the parameter change.

102

Acceleration/Deceleration table creation error

I/O update continuing error

There is a problem with the special I/O parameter you set.

The parameter is not correct. Reset the parameter and request the acceleration/deceleration table creation.

103

Initial parameter error

I/O update continuing error

There is a problem with the special I/O parameter during initial processing.

The parameter is not correct. It will be returned to the initial value set with the editor. Reset the parameter and request the parameter change.

 

Internal error

Error Code

Error Message

Description

Solution

200

Integer type data read error.

I/O update continuing error

Reading the integer type terminal data value failed.

The project file may not have been sent correctly.

Transfer the project file again.

201

Bit type data read error

I/O update continuing error

Reading the bit type terminal data value failed.

202

Integer type data write error

I/O update continuing error

Writing the integer type terminal data value failed.

203

Bit type data write error

I/O update continuing error

Writing the bit type terminal data value failed.