Error Code |
Error Message |
Description |
Solution |
---|---|---|---|
002 |
Illegal parameter |
The data type of the symbol variable assigned to the I/O is incorrect. |
The project file might not have been sent properly. Transfer the project file again. |
003 |
Device offset beyond limit. |
The address of the symbol variable assigned to the I/O is out of range. |
|
004 |
Terminal config overlapped. |
The number of I/O terminals exceeds the limit (6 bit inputs and 2 bit outputs). |
|
005 |
Illegal terminal sequence. |
The I/O terminal numbers are not set up in ascending order. |
|
006 |
Insufficient terminals. |
The number of I/O terminals is not appropriate (insufficient). |
|
009 |
Driver config overlapped. |
The driver has been registered twice. |
|
011 |
Unmatched bit/word term. |
The variable type specified in the I/O is incorrect. |
|
012 |
Illegal level number |
Something is wrong with the I/O driver. |
|
013 |
Illegal data address gotten. |
The I/O driver information is incorrect. The controller information is incorrect. |
|
014 |
Driver/Units not registered. |
The I/O driver or I/O is not registered. |
|
050 |
Different ID unit connected. |
The I/O board being connected is different from the I/O board in the project. |
|
100 |
DIO read data chattering |
Chattering occurred during the input from the DIO board. |
This may be caused by noise or display unit failure. If this error occurs frequently, the unit may be faulty. If the problem continues, please contact our customer care center. |
101 |
DIO write data error |
Although data was output to the DIO board, it was not output when the output result was fed back. |