31.3.3.1 Error Code - DIO Driver

Error Code

Error Message

Description

Solution

002

Illegal parameter

The data type of the symbol variable assigned to the I/O is incorrect.
There is a problem with the I/O setting value.

The project file might not have been sent properly. Transfer the project file again.

003

Device offset beyond limit.

The address of the symbol variable assigned to the I/O is out of range.

004

Terminal config overlapped.

The number of I/O terminals exceeds the limit (6 bit inputs and 2 bit outputs).

005

Illegal terminal sequence.

The I/O terminal numbers are not set up in ascending order.

006

Insufficient terminals.

The number of I/O terminals is not appropriate (insufficient).

009

Driver config overlapped.

The driver has been registered twice.

011

Unmatched bit/word term.

The variable type specified in the I/O is incorrect.

012

Illegal level number

Something is wrong with the I/O driver.

013

Illegal data address gotten.

The I/O driver information is incorrect. The controller information is incorrect.

014

Driver/Units not registered.

The I/O driver or I/O is not registered.

050

Different ID unit connected.

The I/O board being connected is different from the I/O board in the project.

100

DIO read data chattering

Chattering occurred during the input from the DIO board.

This may be caused by noise or display unit failure. If this error occurs frequently, the unit may be faulty. If the problem continues, please contact our customer care center.
This error code continues appearing until the controller is reset.

101

DIO write data error

Although data was output to the DIO board, it was not output when the output result was fed back.