In the [Alarm/Color] tab in the Data Display [Numeric Display], when [Color Specification] is set to [Address], you can change any numeric value colors or plate colors by storing color codes to the address specified.
The color codes that you can use vary depending on the [Color] settings when you click [System Settings], select [Display Unit], and then select the [Display] tab.
5.4.2.2 System Settings [Display Unit] - [Display] Settings Guide
Settings in the [Color] in the [System Settings] |
Display Color |
Usable Color Code Range |
Monochrome 8 Levels, No Blink |
Monochrome 8 Levels, No Blink |
0 to 7 |
Monochrome 8 Levels 1-Speed Blink |
Monochrome 8 Levels, 1-Speed Blink |
0 to 7 |
Monochrome 16 Levels, 3-Speed Blink*1 |
Monochrome 16 Levels 3-Speed Blink |
0 to 15 |
16 Colors, 1-Speed Blink |
16 Colors, 1-Speed Blink |
0 to 15 |
64 Colors, 3-Speed Blink |
64 Colors, 3-Speed Blink |
0 to 63 |
256 Colors, No Blink*2 |
256 Colors, No Blink |
0 to 255 |
4096 Colors, 3-Speed Blink |
64 Colors, 3-Speed Blink |
0 to 63 |
16384 Colors, 3-Speed Blink |
64 Colors, 3-Speed Blink |
0 to 63 |
65535 Colors, No Blink*2 |
256 Colors, No Blink |
0 to 255 |
*1 When you set the [Numeric Value Color] to [0] and [Blink] to [Medium], text is set to transparent.
*2 When you set the [Numeric Value Color] to [255], text is set to transparent.
Time-Base Restrictions
If the device specified in the [Basic] tab's [Monitor Word Address] field is not compatible, the Time-Base function will not work.
If you select the [Time-Base] check box, you cannot change the following items:
Category |
Items |
Fixed Value |
---|---|---|
Basic |
Address Type |
Direct Specification |
Input/Display Range Definitions |
Disable |
|
Data Type |
16 Bit Dec |
|
Sign +/- |
Disable |
|
Round Off |
Disable |
|
Display |
Total Display Digits |
3 |
Decimal Places |
0 |
|
Display Style |
Align Right |
|
Zero Suppress |
Enable |
|
Zero Display |
Enable |
|
Display Format |
Disable |
|
Alarm/Color Settings*1 |
Ranges |
1 |
Area Specification |
Constant |
|
Range Number |
Min: Max: |
|
Alarm Action |
Direct |
|
Processing |
Processing |
Disable |
Allow Input |
Input Barcode |
Disable |
*1If the [Allow Input] check box is selected in the [Basic] tab and the [Fixed Input] check box is not checkmarked in the [Time-Base] group, you cannot change [Alarm] in the [Alarm/Color] tab.
You can set the [Alarm Range] with a value from 0 to 999.
In the middle of a data input from the display unit, even if you change how the defined address stores its data, the input will continue to use the previous input setting. This is not updated in real time.